Penkios bendros šaldymo sistemos problemos
Pirma, nepakankamo šaltnešio valymas
1. Gedimo reiškinys: visos mašinos aušinimo poveikis yra silpnas, vandens išleidimo anga yra tik šiek tiek šalta, o aukšto - ir žemo - slėgio pusėse yra būti žemas su kolektoriaus manometru (esant normaliam kompresoriaus greičiui, kai aplinkos temperatūra yra apie 35 ℃, žemo slėgio) skaitiklio rodiklis yra mažesnis nei 1kg / cm2, aukšto - slėgio matuoklio indeksas yra mažesnis nei 10kg / cm2), o burbulo srautą galima pamatyti iš stebėjimo stiklo.
2. The cause of the failure: the refrigeration system has a refrigerant leakage point, which results in insufficient refrigerant.
3. Treatment method: 1). Use electronic leak detector to find the leak point and repair or replace parts.
2). If the parts are not replaced, only the appropriate amount of refrigerant can be added; if the parts are replaced, the appropriate amount of refrigeration oil should be added as required, and the refrigerant should be added after the system is evacuated.
Antra, per didelis šaltnešio kiekis
1. Failure phenomenon:
Aušinimo poveikis yra silpnas, o aukšto - ir žemo - slėgio pusės slėgis yra per didelis, jei patikrinama su kolektoriaus manometru (kai kompresoriaus greitis yra normalus, o aplinkos temperatūra yra 35 ° C, aukštas - manometro slėgis yra apie 19 kg / cm2, o žemas - manometro slėgis yra 2,3 kg / cm2, o stebėjimo stikle nematyti oro burbuliukų. .
2. Failure reason: Too much refrigerant is added in the refrigeration system, so that the refrigeration capacity cannot be fully exerted, resulting in poor refrigeration effect.
3. Treatment method: Connect the manifold pressure gauge to the system, and slowly loosen the manual valve on the low pressure side of the manifold pressure gauge, so that the refrigerant is slowly discharged (cannot be discharged from the high pressure side, because the refrigerant will be taken out from the high pressure side) A large amount of freezing oil) until the pressure on the high and low sides is normal, and the refrigerant flows clearly from the sight glass, and occasionally bubbles flow through.
Trečia, aušinimo sistema sumaišoma su oru
1. Gedimo reiškinys: sumažėja visos mašinos aušinimo galia; kai tikrinamas kolektoriaus manometras, slėgis aukšto slėgio pusėje yra didelis, o žemo slėgio pusėje slėgis kartais gali būti didesnis nei normalioji vertė (kompresoriaus greitis yra normalus, o aplinkos temperatūra yra 35 ° C) Šiuo metu aukšto - slėgio pusės slėgis yra didesnis nei 20 kg / cm2, o aukšto - slėgio matuoklio rodyklė svyruoja, kita vertus, matosi, kad teka daugybė burbuliukų. iš akinių stiklo.
2. Reasons for failure:
Oras yra maišomas sistemoje. Dažniausiai po surinkimo ar kapitalinio remonto vakuumas nėra išsamus; kraunant šaltnešį ar pridedant šaldymo alyvos, į sistemą patenka oras arba, kai sistema veikia esant neigiamam slėgiui, oras maišomas per sandarias vietas. Kai šaltnešis patenka į orą, jis turi tam tikrą slėgį, o šaltnešis taip pat turi tam tikrą slėgį. Uždaroje talpykloje bendras dujų slėgis yra lygus dalinių slėgių sumai, todėl aukšto ir žemo slėgio matuoklio rodmenys yra didesni nei įprasta.
3. Treatment method: 1) Release refrigerant (release slowly from low pressure side with pressure gauge). 2) Check the cleanliness of the compressor oil. 3) Refill the refrigerant after vacuuming.
Fourth, & quot;ice blockage & quot; appears in the refrigeration system
1. Failure phenomenon: The refrigeration system periodically cools suddenly but not suddenly. During operation, the pointer on the low pressure side of the manifold pressure gauge often fluctuates between the negative pressure and the normal value.
2. Cause of failure: Moisture is mixed into the refrigerant in the refrigeration system. Because the water is incompatible with the refrigerant, when the refrigerant flows through the orifice of the expansion valve, the temperature drops suddenly. These are mixed in the refrigerant The water will easily form small particles of ice in the vicinity of the small hole of the throttle valve or around the valve pin hole, which is spherical or hemispherical. When the ice particles are condensed to a certain extent, the throttle channel is blocked and an ice jam fault is formed. . When ice blocking occurs due to icing, the refrigeration system cannot work properly, and the refrigeration effect is significantly reduced, even without refrigeration.
Šiuo metu žemo slėgio matuoklyje pasirodė neigiamas slėgis, todėl ledo bloko temperatūra akivaizdžiai pakilo, ledo bloko ledo dalelės ištirpo vandenyje, todėl ledo bloko reiškinys išnyko, šaldymo sistema vėl pradėjo veikti normaliai. šaldymas buvo geras, o žemo slėgio šoninis slėgis normalizavosi. Po kurio laiko sistemoje užsikimšo ledas ir sistema neveikė tinkamai.
3. Treatment method: 1) Because the desiccant is in supersaturated state, it is necessary to replace the reservoir with desiccant and add 30ml of freezing oil. 2) Vacuum the system and add a specified amount of refrigerant.
Penkta, nešvarių užsikimšimų šalinimas
1. Failure phenomenon: poor cooling effect or no cooling. When the air conditioning system is running, the readings of the high and low pressure gauges on the manifold pressure gauge are less than the normal value. (When the compressor speed is normal and the ambient temperature is around 35 ° C, the pressure on the high pressure gauge side is less than 9 kg / cm2, and the pressure on the low pressure side is Negative pressure), and there is frost or dew on the filter and capillary tube.
2. The cause of the failure: the dust in the refrigeration system adheres or adheres to the filter screen at the inlet end of the filter, or the interface between the capillary and the filter screen, so that a local throttling phenomenon is formed at this location, and the temperature drops rapidly, and condensation or condensation occurs Frost.
3. Treatment method: If there is frosting at the filter inlet, and the sound of intermittent airflow is heard, tap the filter body with a small wrench, the airflow sound changes, and the frost layer of the filter and capillary melts at the same time, which can be judged The filter inlet filter is clogged.
Šiuo metu: ① Nuimkite kapiliarą, išvalykite filtrą, nusausinkite ir vėl įstatykite. Arba pakeiskite filtrą ② ištuštinkite ir užpildykite šaltnešį iki nurodyto kiekio.